The Ridgway Water Treatment Plant (WTP) in Elk County Pennsylvania uses a Real Tech Real UV254 online analyzer to achieve a 20-30% savings in annual coagulant use in their conventional water treatment process. Equipped with Real Tech’s dual-feed feature, the Real UV254 analyzer is used to continuously monitor raw and finished water dissolved organics via a single online analyzer. Beyond operational cost savings, the Real UV254 system helps the WTP consistently produce high quality drinking water for the town’s 1700 customers.
Background
The Ridgway WTP receives water from a spring-fed source on Big Mill Creek in rural north-central Pennsylvania near the Allegheny National Forest. Raw water from the creek is fed into the 272 million-gallon H.B. Norton Reservoir before being fed to the WTP. From there, the city’s 2 MGD (7.5 MLD) conventional coagulation, flocculation, sedimentation treatment process handles treatment. Raw water entering the process is dosed with polyaluminum chloride (PAC) for coagulation and soda ash (sodium carbonate) for pH control. Both gas chlorine and permanganate (KMnO4) are also dosed to achieve better organics control in the conventional process. Settled water is then fed to one of five (5) conventional dual-media (sand + anthracite) filters for filtration prior to final stabilization and disinfection before distribution. Overall, the process continues to provide excellent water treatment for its community.
Improving performance with UV254
Although raw water to the plant is of generally high quality, periodic turbidity spikes and seasonal variation of dissolved organics entering the process have posed operational challenges. Looking for ways to improve performance, Rick McKnight, Ridgway’s Water Plant Supervisor, decided to explore UV254 instruments in the summer of 2012. Before starting to monitor UV254, the plant looked at turbidity on the raw water. “We would have high colour in the water that wasn’t picked up with turbidity” said McKnight “ As a result sometimes we were either over-, or under-dosing coagulant which led to filtration and other operating issues.”
Based on his research and many years experience operating the plant, McKnight took a proactive approach by putting data from his Real UV254 field meter into action. After five (5) years of very promising results the WTP installed a dual-feed Real UV254 online analyzer to monitor both raw and settled water in 2017. Now with years of continuous operating data the plant has developed a firm relationship between raw water UV254 and coagulant dose. Being able to monitor organics and adjust their coagulant has made a big impact for the plant.
“Our coagulant is a fairly expensive part of our operating costs. Now, if we see a good raw water UV254 number, we know we can cut back to save costs. The savings have been pretty significant and we’re regularly saving 20-30% on coagulant use throughout the year.”